Prelia Cleanroom

REFERENCE

ISO 14644 classification and GMP grades

Two systems, one room. This is how they line up.

ISO 14644-1 LIMITS

Maximum particles per cubic metre

Class ≥0.5 µm ≥1.0 µm ≥5.0 µm Former US FS 209E
ISO 5 3,520 832 Class 100
ISO 6 35,200 8,320 293 Class 1,000
ISO 7 352,000 83,200 2,930 Class 10,000
ISO 8 3,520,000 832,000 29,300 Class 100,000

Limits per ISO 14644-1:2015. FS 209E was withdrawn in 2001 and is shown only because it is still in daily use.

GMP GRADE MAPPING

GMP grade to ISO class

GMP grade At rest In operation
A ISO 5 ISO 5
B ISO 5 ISO 7
C ISO 7 ISO 8
D ISO 8 Not predefined

Per PIC/S and EU GMP Annex 1. A room that meets its grade at rest can still fail in operation, which is why both states are stated.

INDICATIVE DESIGN VALUES

Typical design values

Class Air changes per hour Filtration
ISO 6 90–180 HEPA, terminal
ISO 7 30–60 HEPA, terminal
ISO 8 15–30 HEPA or high-efficiency

Differential pressure between adjacent classified areas is commonly designed at 10 to 15 Pa.

These are indicative ranges for early planning. Actual values are set by the room's heat load, occupancy, process and recovery requirement.

ISO CLASS 7

ISO Class 7 in practice

ISO Class 7 is where most regulated assembly and packing work sits in Malaysia. It permits 352,000 particles of 0.5 µm or larger per cubic metre, typically runs at 30 to 60 air changes per hour, and needs terminal HEPA filtration throughout. Stepping up from ISO 8 to ISO 7 roughly doubles the air you move, and that difference stays on your energy bill for the life of the room.

WHICH CLASS DO I NEED

Choosing a class

Work backwards from the product. Ask what is exposed, for how long, and what the regulator expects for that product type. Over-specifying by one class raises air change rates and runs up energy cost for the life of the room.

Talk it through with us

NEXT STEP

Tell us the classification you need.

Send your floor area, target ISO class and process. We reply with a scope outline and an indicative range.